Sensible Equipment Company, Inc.

TRICOIL® Air Conditioning Method
The Sensible Solution
TM

P.O. Box 669 Goldenrod, FL  32733  ·  tel: 407-296-8068  ·  fax: 407-296-7420  ·  email: kle@tricoil.com

Home Up

 

 

TRICOIL® COMPARISON

To effectively provide a comfortable indoor environment, an air conditioning system must provide cooling as well as dehumidification. 
The following example illustrates the effectiveness of the TRICOIL® system as compared to a traditional system.

Example
An air conditioning system is required to provide 10,000 CFM of supply air to cool a room to 76°F and 45 % RH. The room sensible heat factor is 0.80 and the amount of outside air required is 2000 CFM. Calculations show that 8 °F of reheat is required to maintain the desired indoor relative humidity and to bring the supply air to 70% relative humidity as recommended in ASHRAE Standard 62-1989. The traditional system uses electric reheat and the TRICOIL® system uses the patented TRICOIL recuperative process.

SUMMARY
TRADITIONAL SYSTEM WITH 
ELECTRIC
HEAT
TRICOIL® METHOD
AIR VOLUME
10,000 CFM
10,000 CFM
PRIMARY COOLING
41.1 TONS
34.1 TONS
MOISTURE REMOVAL
117.0 LBS/HR
117.0 LBS/HR
POWER REQUIRED:
 
 
  CONDENSING UNIT
46.9 KW
37.5 KW
  SUPPLY AIR FAN
5.0 KW
5.2 KW
  ELECTRIC REHEAT
25.8 KW
0 KW
  TRICOIL PUMP
0 KW
0.2 KW
  TOTAL
77.7 KW
42.9 KW
EFFICIENCY:
 
 
  TOTAL COOLING (1)
1.89 KW/TON
1.25 KW/TON
  DEHUMIDIFICATION (2)
10.54 GR/W
19.09 GR/W

RESULTS
The TRICOIL® method uses only 55% of the power that the traditional system uses to cool and dehumidify this room.

Notes
  (1) The Total Cooling efficiency is based on the total power required to cool and dehumidify the room including the electric reheat energy.
  (2) The dehumidification efficiency is a new method for ranking air conditioning systems based on their moisture removal capability. The units "GR/W" are 
       Grains of Moisture Removed per Total Watts of Power Input. There are 7000 grains of moisture in a pound of water.

PSYCHROMETRIC CHART
The following chart indicates the process of a typical TRICOIL® operation such as the 
one illustrated in the above example.


USA patent numbers 
5,181,552; 5,228,302; 5,337,577
Other USA and foreign patents pending.
STATE POINTS
a. Room Condition 76°F DB/62.0°F WB/45%RH
b. Outside Air 93°F DB/80.0°F WB
c. Mixed Air; 80°F DB/67.0°F WB
d. Precooled Air 72°F DB/64.2°F WB
e. Primary Air 50°F DB/49.8°F WB
f. Reheated Air 58°F DB/53.5°F WB
g. Supply Air 60°F DB/54.5°F WB/70%RH

PROCESS
1. Precooling 88 MBH
2. Primary Cooling 409 MBH
3. Reheat 88 MBH
4. 2°F Allowance for Fan And Motor Heat Gain

 

 
Send mail to kle@tricoil.com with questions or comments about this web site.
Copyright © 2009 Sensible Equipment Compnay, Inc.
Last modified: August 05, 2009