PUMP
OFF |
PUMP
ON |
| AIR
VOLUME |
10000
CFM |
10000
CFM |
ENTERING
AIR TEMPERATURE
HUMIDITY RATIO |
80°F
DB / 67°F WB
0.0113 lb water / lb dry air |
80°F
DB / 67°F WB
0.0113 lb water / lb dry air |
SUPPLY
AIR
TEMPERATURE
DEWPOINT
HUMIDITY RATIO |
55°F DB / 53.8°F WB
53°F Dewpoint Temp
0.0085 lb water / lb dry air |
59.5°F DB / 53.8°F WB
49.5°F Dewpoint Temp
0.0075 lb water / lb dry air |
UNIT
COOLING PERFORMANCE
SENSIBLE
LATENT
TOTAL
UNIT SENSIBLE HEAT RATIO |
293.0 MBH
134.2 MBH
427.2 MBH
.69 SHR |
244.1 MBH
183.1 MBH
427.2 MBH
.57 SHR |
ROOM
COOLING EFFECT
SENSIBLE
LATENT
ROOM SENSIBLE HEAT RATIO |
217.0 MBH
38.7 MBH
.85 SHR |
168.2 MBH (22% decrease)
87.1 MBH (123% increase)
.66 SHR |