TEMPERATURE/CONTROL
RESPONSE FOR TRICOIL®
METHOD

USA patent
numbers 5,181,552; 5,228,302; 5,337,577. Other USA and foreign patents pending.
|
Cooling:
|
First
stage of cooling: The chilled water valve shall modulate to maintain
the room temperature setpoint. On a rise in room temperature the chilled
water valve shall modulate open and on a drop in room temperature the
valve shall modulate closed.
Second Stage of Cooling: Cycle the TRICOIL® pump on
and off for the second stage of cooling. When the chilled water valve is
100% open and on a further rise in room air temperature above the first
stage setpoint, stop the TRICOIL® pump. On a drop in room
air temperature start the pump.
|
|
Heating:
|
The
hot water valve shall modulate to maintain the room air temperature
setpoint. On a drop in room air temperature the heating hot water valve
shall modulate open and on a rise in room air temperature the valve
shall modulate closed.
|
|