GENERAL
FEATURES
These
are some general paragraphs that are use to clarify and supplement
the TRICOIL® specifications.
ENHANCED
HUMIDITY CONTROL SYSTEM
Where
specified or where indicated on the drawings, provide an enhanced
humidity control system as described herein. The base bid system
shall be the patented TRICOIL® method of air conditioning for
enhanced temperature and humidity control. The TRICOIL® components
shall be furnished as a coordinated package by the air handling
unit manufacturer. Contact Sensible Equipment Company, P.O. Box
669, Goldenrod, Florida 32733, telephone number (407) 296 - 8068,
Fax Number (407) 296 - 7420.
Alternates
to the base bid are encouraged. The contractor may furnish, with
the engineers approval, a deductive alternate to the base bid to
use other equipment or methods that provides performance as scheduled.
Alternate bids must be submitted in writing with complete engineering
analysis including equipment performance data, psychrometric analysis
with chart, flow diagrams, equipment specifications, manufacturer's
descriptive literature, reduction in bid amount, and other information
required by the engineer to analyze the proposed alternate. The
alternate must include any and all costs for the work of other trades
required to provide complete and operational equivalent systems.
The contractor shall assume single source responsibility for all
the subsystems that he chooses to integrate and submit for his alternate
bid. All responsibilities for equivalencies for the performance
of the alternate system or method to the base bid system or method
plus the coordinated supporting central plant utilities (electrical
and/or mechanical) plant shall constitute a required single source
responsibility and shall be so acknowledged by the contractor with
the alternate proposal.
The
air handling units shall have the following features:
- TRICOIL®
method of enhanced humidity control having capacities as indicated
or scheduled with components as specified and/or indicated on
the drawings.
- Primary
cooling coil shall be chilled water or direct expansion cooling
as specified.
- A recuperative
precooling/reheat system shall be provided that shall exchange
energy from the mixed outside air and return air stream (or the
100% outside air stream as applicable) to the supply air stream
for simultaneous precooling and reheating. The base bid system
shall use a hydronic piping loop and circulating pump. Alternate
systems may use a desiccant heat exchanger, heat pipe loop, or
an air to air heat exchanger. Space shall be provided between
each coil and heat exchange surface for cleaning. A method of
controlling the amount of energy exchange from 0% to 100% of rated
capacity between the reheat and precooling elements shall be provided
for part load performance.
- Supplemental
reheat: The base bid TRICOIL® method shall use the hydronic
reheat coil to provide the supplemental reheat energy to the supply
air stream. The supplemental reheat energy shall be from the hot
water source as indicated on the drawings.
- Preheat:
The base bid TRICOIL® method shall use the precooling coil
to provide the preheat function to provide preheat energy for
freeze protection and heating duty as required. The heating energy
shall be from the hot water source as indicated on the drawings.
- Coordinate
access door locations with the air handling unit manufacturer.
Access space must be provided between each coil for servicing
and cleaning purposes. Provide service doors in access sections.
TRICOIL®
METHOD KITS FOR FIELD ASSEMBLY
The TRICOIL®
method is a recuperative wrap around type system providing simultaneous
precooling and reheat for temperature and humidity control. The
TRICOIL® method shall also provide heating and supplemental reheat
control where indicated. The TRICOIL® method Kits include components
which shall be field assembled and wired by the installing contractor.
The TRICOIL® method Kits shall consist generally of the following
components:
- Site specific
license for the specified TRICOIL® system with capacity as
scheduled or as indicated.
- Pump and
motor, pump motor starter for three phase motors and pump control
relay for single phase motors.
- TRICOIL®
loop control valves with actuators. Quantity, and type of valves
and actuators shall be as required to match the operating sequence
and as indicated on the drawings. (Chilled Water Control Valve
is not included with the TRICOIL® components and shall be
provided by the temperature control contractor).
- TRICOIL®
loop water balancing valve shall be a circuit setter type or flow
control type as indicated. The heating hot water flow control
valve, where indicated, shall be an automatic flow control type.
TRICOIL®
METHOD PUMP/VALVE ASSEMBLIES
The TRICOIL®
method is a recuperative wrap around type system providing simultaneous
precooling and reheat for temperature and humidity control. The
TRICOIL® method shall also provide heating and supplemental reheat
control where indicated. The TRICOIL® method components shall
be provided for field installation and wiring by the installing
contractor. The TRICOIL® method components shall consist generally
of the following:
- Site specific
license for the specified TRICOIL® system with capacity as
scheduled or as indicated.
- Pump and
Valve Assemblies complete with pump and motor, pump motor starter,
differential pressure switch, control valve(s), balancing valve(s),
and piping with drain and vent. Components shall be factory assembled
in an insulated enclosure with a drain pan. Pump motor, starter,
control valve(s), pressure switch, pump status light, and hand/off/auto
switch shall be factory wired to a numbered terminal strip ready
for connection to the electrical power supply and to the temperature
control system.
- TRICOIL®
loop control valves with actuators. Quantity, and type of valves
and actuators shall be as required to match the operating sequence
and as indicated on the drawings.
- TRICOIL®
loop water balancing valve shall be a circuit setter type and
heating hot water flow control valve, where indicated, shall be
an automatic flow control type.
PUMPS FOR
KITS AND ASSEMBLIES
The pump shall
be an In-line type or In-line Booster type as scheduled or other
approved. Pump characteristics shall be as scheduled on the drawings.
- · In-line
Pumps shall be Bell and Gossett Series 80 or other approved. Pumps
shall be suitable for vertical or horizontal installation. Pumps
shall be close coupled, single stage design and shall be capable
of being serviced without disturbing the piping. Pump casing shall
be Class 30 cast Iron. Impeller shall be cast bronze, enclosed
type and shall be dynamically balanced. Pumps shall be rated for
175 psig working pressure. Pumps shall have gauge tappings at
the suction and discharge nozzles and shall include vent and drain
proof ports. Motors shall be Totally Enclosed, and shall meet
NEMA specifications. The motors shall be non-overloading at any
point on the pump's performance curve. Pumps shall be factory
tested. Pumps shall be factory painted with high-grade machinery
enamel paint.
- · Inline
Booster Pumps shall be Bell and Gossett Series PL or other approved.
Pumps shall be of the horizontal, permanently lubricated type
with steel shaft, ball bearings, and water tight seals. Pump body
shall be cast iron or bronze, face plate shall be stainless steel.
Impeller shall be non-metallic. Mechanical seal faces shall be
carbon on silicon carbide. The motor shall be non-overloading
at any point on the pump performance curve. The pump motor shall
be open drip proof, sealed ball bearing, quiet operating construction
the motors shall be split capacitor type with thermal overload
protection. Pumps shall be suitable for operation at 225 degrees
F at 150 psig working pressure.
- · The pump
shall be a Taco Cartridge Circulator pump or other approved and
shall have a bronze casing, a non-metallic impeller, a ceramic
shaft, flanged connections, permanent split capacitor motor with
overload protection. Pump and motor shall be selected for non-overloading
operation. Pump characteristics shall be as scheduled on the drawings.
VALVES FOR
KITS AND ASSEMBLIES
The valves used
in the TRICOIL® system shall be of the type as scheduled or
other approved. Characteristics shall be as scheduled on the drawings.
- Control valves
(Plan Mark CV) shall be three port ball valves as indicated on
the drawings. Valves shall have bronze bodies with female NPT
threads. Valves shall have blowout proof stem design, glass reinforced
Teflon thrust seal washer and stuffing box ring with minimum 400
psi rating. Stem packing screw shall be adjustable for wear. Valve
ball shall be chromium plated bronze and shall be rated at a minimum
of 400 psi WOG, cold, non-shock service. All valves shall be provided
with reinforced Teflon seats.
- Control valve
actuators shall be fully modulating or two position as indicated
in the control sequence. Modulating valves shall be positive positioning,
responding to a 2-10 VDC or a 4-20 mA signal (with the addition
of a 500 ohm resistor). There shall be a visual valve position
indicator and an actuator generated 2-10 VDC valve position output
signal for electronic feed back to the control system. Valve power
required shall be 24 VAC and power consumption shall not exceed
8 watts at 24 VAC. The actuator shall provide minimum torque required
for proper valve close-off. The actuator shall be designed for
use with current limiting motor overload protection or shall have
adjustable single pole double throw travel stop limit switches.
A release button or handle on the motor shall be provided to allow
for manual override, except when using spring return valves. All
valves shall be UL listed.
- Balancing
Valve, (Plan Mark BV) shall be a circuit setter type balancing
valve as made by Taco or other approved. The valve shall be bronze
body through 2 inch diameter, all brass interior parts, sweat
or NPT pipe connections, schrader style pressure ports for attachment
to a differential pressure gauge, (gauge not included), drain
port, blow-out proof stem, calibrated nameplate with tamper resistant
memory stop, and o-ring seal. Valves through 2 inch diameter shall
be rated to 300 PSI, 250 degrees F.
- Flow Control
Valve (Plan Mark FCV) shall be a Griswold Miniature style flow
control valve or other approved capable of controlling flow to
within +/- 5% accuracy through the specified pressure differential
range of the valve. Valve body shall be ductile iron body through
1.5 inch diameter and flow rates from 0.33 to 34 GPM and shall
have female NPT end connections, stainless steel flow control
assembly, dual 1/4 inch pressure/temperature test valves for measuring
pressure or temperature in the system (gauges not included), shall
be permanently marked to show direction of flow, model number
and differential pressure control range.