Pre-assembled, patented, TRICOIL® pump and valve assemblies.


TRICOIL
®Pump and Valve Assemblies: The TRICOIL® Pump and Valve Assemblies are pre-engineered to satisfy a majority of applications. There are eight standard variations of the Pump and Valve Packages. Other arrangements can be accommodated as specials.

Series

Description

TP

TRICOIL® Pre-assembled Pump and Valve Packages: TRICOIL® Pumps, Valves and other components are pre-assembled in insulated cabinets and delivered to the job site ready for final installation in the piping system


Hand indicates the side of the assembly that the heating hot water connections are on.

Type/Description

TP-A

Single pump and one 3-way control valve. Recuperative water flow is constant. Hot water flow rate is variable. Typically used with local hot water heat source where pressure for hot water flow is provided by the TRICOIL® pump.

TP-B

Single pump and one 2-way control valve. Recuperative flow is constant. Hot water flow is variable. Typically used with central heating hot water plants which have there own variable volume pumping systems. The TRICOIL® pump does not provide pressure differential for hot water flow.

TP-C

Single pump and one 3-way control valve. Recuperative flow is constant. Hot water flow is constant. Typically used with central heating plants which have there own constant volume pumping system. TRICOIL® pump does not provide pressure differential for hot water flow.

TP-D

Two pumps and one 3-way control valve. Recuperative flow is constant. Hot water flow is constant. Typically used with local heating plants that require more pump head than is available from the recuperative loop pump.

TP-E
Single pump and two 3-way control valves. Recuperative water flow is variable through the reheat coil. Hot water flow rate is variable. Typically used with local hot water heat source where pressure for hot water flow is provided by the TRICOIL® pump.
TP-F
Single pump, one 3-way control valve, and one 2-way control valve. Recuperative water flow is variable through the reheat coil. Hot water flow is variable. Typically used with central heating plants which have there own variable volume pumping system. The TRICOIL® pump does not provide pressure differential for hot water flow.
TP-G
Single pump and one 3-way control valve. Recuperative water flow is variable through the reheat coil. Hot water flow is constant. Typically used with central heating plants which have there own constant volume pumping system. TRICOIL® pump does not provide pressure differential for hot water flow.
TP-H
Two pumps and two 3-way control valves. Recuperative water flow is variable through the reheat coil. Hot water flow is constant. Typically used with local heating plants that require more pump head than is available from the recuperative loop pump.

Table 1: TRICOIL® Pump and Valve Assemblies:
Size
Air Volume
Water Data
Pump Motor Horsepower
CFM, CAV
CFM, VAV
Recuperative Loop
Heating Loop
GPM (1)
Loop "A"
Loop "B" Select One
02
925
1320
2.0
½
½
1/12
06
2780
3970
6.0
¾
½, ¾
1/6
12
5560
7940
12.0
1
½, ¾
1/6
14
7410
10580
16
½, ¾, 1
1/6
21
10185
14550
22
½, ¾, 1, 1¼
1/6
30
16670
23810
36
2
½, ¾, 1, 1¼,1½
2 at 1/6

  1. The water flow rates indicated are maximum for the indicated model number. The actual flow is determined by the size of the flow control valve used in the assembly. Available flow rates for each size are as indicated below:

    Size 02 GPM = 0.33, 0.5, 0.67, 1.0, 1.33, 1.67, or 2.0
    Size 06 GPM = 2.33, 2.5, 2.67, 3.0, 3.33, 3.5, 4.0, 4.67, 5.0, or 6.0
    Size 12 GPM = 6.67, 7.33, 8.0, 8.67, 9.33, 10.0, 10.67, 11.33, or 12.0
    Size 14 GPM = 13.0, 13.33, 14.0, 14.67, 15.0, or 16.0
    Size 21 GPM = 17.0, 18.0, 19.0, 20.0, 21.0, or 22.0
    Size 30 GPM = 24.0, 26.0, 28.0, 30.0, 32.0, 34.0, or 36.0

  2. Specify hot water connection size. The hot water flow rate can be no greater than the recuperative water flow rate. The available hot water flow for each connection size is as follows:

    ½" Diameter GPM = 0.33, 0.5, 0.67, 1.0, 1.33, or 1.67
    ¾" Diameter GPM = 2.0, 2.33, 2.67, 3.33, 4.0, 4.67, 5.33, or 6.0
    1" Diameter GPM = 6.67, 7.33, 8.0, 8.67, 9.33, 10.0, 10.67, 11.33, or 12.0
    1¼" Diameter GPM = 13.0, 13.33, 14.0, 14.67, 15.0, 16.0, 17.0, 18.0, 19.0, 20.0, 21.0, or 22.0
    1½" Diameter GPM = 24.0, 26.0, 28.0, 30.0, 32.0, 34.0, or 36.0

  3. The pressure available is the total pressure for two coils piped in series flow. The pressure available has been adjusted to account for a maximum of 100 equivalent feet of pipe at the maximum water flow rate for pipe and fittings external to the pump and valve assembly.

  4. Maximum Air Volume for Variable Air Volume (VAV) Systems is typically 70% greater than for Constant Air Volume (CAV) Systems.

  5. Motor electrical data is 120 volts, 60 Hertz, single phase for all sizes.

Available Pressure for Various Assembly Types: The different assembly types have different pressure available for the precooling and reheat water side pressure drop.


Table 2:

Size
Pressure Drop Available for Coils Ft.WC (1)
Add to Available Pressure when Recuperative Loop Flow Control Valve is not used. Ft WC
Type A, F, G, H
Type B, C, D
Type E
02
5.1
7.4
2.8
2.3
06
7.9
10.2
5.6
4.6
12
6.5
8.8
4.2
2.3
14
7.0
10.0
4.0
4.6
21
4.9
7.4
2.3
4.6
30
4.2
7.5
2.9
9.3
  1. The indicated pressure drop is for both the precooling and reheat coils piped in series taking into account 100 equivalent feet of pipe at the maximum flow rate.

TRICOIL® Pump Package Selection Procedures

STEP 1 CALCULATE RECUPERATIVE WATER FLOW RATE, GPM.

The recuperative water flow rate is proportional to the supply air flow rate for the majority of applications. Use standard engineering cooling load calculations to determine the supply air volume required. For Constant Air Volume (CAV) systems, multiply the supply air volume times the conversion factor, 0.00216 GPM/CFM, to determine the required recuperative water flow rate. For Variable Air Volume (VAV) systems multiply the supply air volume by 0.7 (for part load selection) then multiple by 0.00216.

Example:

If the required air volume is 10,000 cfm the recuperative flow rate would be found using the following equation.

 

Supply Air Volume, CFM x 0.00216 =GPM (Recuperative Flow Rate)

 

10,000 CFM x 0.00216 GPM/CFM = 21.6 GPM

STEP 2 SELECT PUMP/VALVE ASSEMBLY SIZE.

To select the Pump Package size match the recuperative flow rate calculated in STEP 1, above, to the Flow Rate Column in the Selection Table. If there is no exact match use the next higher GPM value. Read the size of the Pump/Valve assembly next to the Available Flow Column. Select the actual flow in the recuperative loop by using note 1. Round off the recuperative flow rate to the closest value found in note 1.

Example:

The required recuperative flow rate calculated in STEP 1 is 21.6 GPM. Refer to Table 1: TRICOIL® Pump and Valve Assemblies above. In the column "Flow Rate, GPM" 21.6 GPM falls between 16 GPM and 22 GPM. The required Pump/Valve Assembly Size therefore is a size 22. Refer to note one of the table and use 22 gpm for the recuperative flow.

STEP 3 DETERMINE PRESSURE DROP AVAILABLE FOR COILS

The pressure drop available for precooling and reheat coils is indicated in the "Available Pressure" Column of Table 1 when Type A assemblies are used. Refer to Table 2 when type B thru type H are used.

STEP 4 SELECT HOT WATER FLOW RATE

The hot water flow rate can be as high as the recuperative water flow rate. Flow control valves are also used in the heating hot water circuit to automatically balance to the specified hot water flow rate. The available water pipe connection sizes are indicated in Table 1 and the available flow rates are indicated in note 2.

TYPICAL AIR HANDLING UNIT WITH TRICOIL® PACKAGE PUMP AND VALVE ASSEMBLY


TRICOIL® PIPING DIAGRAM One or more of the following patents are applicable: 5,181,552; 5,228,302; 5,337,577; 5,493,577. Other U.S. and foreign patents are pending.


TYPICAL TRICOIL PUMP/VALVE PACKAGE SCHEDULE
TAG
Model
PUMP DATA
PIPE SIZE
Pipe "A"
Pipe "B"
Pipe "C"
Size
HP
(120v/60hz/
1phase)
"A", Inch Dia
GPM
"B" Inch Dia.
GPM
"C" Inch Dia.
GPM
TC-1
TP-A-02
1/12
1/2
2.0
1/2
1.0
3/4
7.0
TC-2
TP-C-06
1/6
3/4
6.0
3/4
3.33
1-1/2
20
TC-3
TP-D-14
1/6
1-1/4
16
1
10
2
55
TC-4
TPA-30
2 at 1/6 each
2
36
1-1/4
18
3
120
 

SENSIBLE EQUIPMENT COMPANY, INC.

P.O. BOX 669, GOLDENROD, FLORIDA 32733

PH  (407) 296-8068     FAX  (407) 296-7420

EMAIL  kle@tricoil.com

 

TRICOIL®

 

 

 

             HomePerformanceControlsApplicationsSpecificationsProductsLiteratureFAQContact Us

 

PRE-ASSEMBLED PUMP AND VALVE ASSEMBLIES

 

Products Main

Kits

Pre-Assembled

Package Units

Worksheet