SENSIBLE EQUIPMENT COMPANY, INC.

P.O. BOX 669, GOLDENROD, FLORIDA 32733

PH  (407) 296-8068     FAX  (407) 296-7420

EMAIL  kle@tricoil.com

 

TRICOIL®

 

 

 

             HomePerformanceControlsApplicationsSpecificationsProductsLiteratureFAQContact Us

 

 

Benefits

TRICOIL® COMPARISON: To effectively provide a comfortable indoor environment, an air conditioning system must provide cooling as well as dehumidification. The following example illustrates the effectiveness of the TRICOIL® system as compared to a traditional system.

Example: An air conditioning system is required to provide 10,000 CFM of supply air to cool a room to 76°F and 45 % RH. The room sensible heat factor is 0.80 and the amount of outside air required is 2000 CFM. Calculations show that 8 °F of reheat is required to maintain the desired indoor relative humidity and to bring the supply air to 70% relative humidity as recommended in ASHRAE Standard 62-1989. The traditional system uses electric reheat and the TRICOIL® system uses the patented TRICOIL recuperative processs.

SUMMARY
TRADITIONAL SYSTEM WITH ELECTRIC HEAT
TRICOIL® METHOD
AIR VOLUME
10,000 CFM
10,000 CFM
PRIMARY COOLING
41.1 TONS
34.1 TONS
MOISTURE REMOVAL
117.0 LBS/HR
117.0 LBS/HR
POWER REQUIRED:
 
 
CONDENSING UNIT
46.9 KW
37.5 KW
SUPPLY AIR FAN
5.0 KW
5.2 KW
ELECTRIC REHEAT
25.8 KW
0 KW
TRICOIL PUMP
0 KW
0.2 KW
TOTAL
77.7 KW
42.9 KW
EFFICIENCY:
 
 
TOTAL COOLING (1)
1.89 KW/TON
1.25 KW/TON
DEHUMIDIFICATION (2)
10.54 GR/W
19.09 GR/W

RESULTS: The TRICOIL® method uses only 55% of the power that the traditional system uses to cool and dehumidify this room.

Notes:
(1) The Total Cooling efficiency is based on the total power required to cool and dehumidify the room including the electric reheat energy.
(2) The dehumidification efficiency is a new method for ranking air conditioning systems based on their moisture removal capability. The units. "GR/W" are Grains of Moisture Removed per Total Watts of Power Input. There are 7000 grains of moisture in a pound of water.

PSYCHROMETRIC CHART: The following chart indicates the process of a typical TRICOIL operation such as the one illustrated in the above example.


USA patent numbers 5,181,552, 5,228,302 5,337,577. Other USA and foreign patents pending.
STATE POINTS
a. Room Condition 76°F DB/62.0°F WB/45%RH
b. Outside Air 93°F DB/80.0°F WB
c. Mixed Air; 80°F DB/67.0°F WB
d. Precooled Air 72°F DB/64.2°F WB
e. Primary Air 50°F DB/49.8°F WB
f. Reheated Air 58°F DB/53.5°F WB
g. Supply Air 60°F DB/54.5°F WB/70%RH

PROCESS
1. Precooling 88 MBH
2. Primary Cooling 409 MBH
3. Reheat 88 MBH
4. 2°F Allowance for Fan And Motor Heat Gain

 

 

Comparisons

Installations

Loop Runaround

Basic Control

Patent Info